The controller is intended for supervising and automating the different variables which are used in the operation of paint booths or similar.

General Characteristics

  • Visualisation using LCD graphic display with high contrast and brightness with a resolution of 64x128 pixels.
  • It uses 2 temperature inputs of Pt 1000 to measure 2 points in the booth. One is used for the regulation of the booth temperature. The other probe measures the maximum or minimum alarm temperatures.
  • It has the possibility of measuring the temperature of the part to be painted using a third Pt 1000 probe.
  • Possibility of measuring the booth pressure using an internal pressure sensor or an external converter with 4/20 mA.
  • It includes two built-in differential pressure sensors to detect the correct condition of the filters.
  • This allows measuring the relative humidity of the booth.
  • By configuring the analogue control equipment signals there is allocation to each of the four analogue outputs with 0/10 V.
  • Direction operation using a relay of up to 4 lines of lights inside the booth.
  • RS485 output for communication with SW6000.

Electric

  • Power supply 24 Vac +/- 20%. (50-60 Hz)
  • Electric consumption: 5VA.
  • Outputs by relay 3 Amp. 230VAC potential-free.
  • Analogue outputs at 0/10 V.
  • Voltage output +24Vcc maximum load 75mA for supplying external converters.
  • Temperature inputs probe type Pt1000.
  • Inlet of RH for the sensor with power supply +5 Vcc.
  • Signal inputs from linearised transmitter 4...20 mA with incorporated power supply 24Vcc.
  • Direct inputs of differential pressure sensors.

Mechanical

  • Format 300x230 mm.
  • Depth 60 mm including the connection terminals.
  • Front protection IP65.
  • Rear protection IP00 (interior protection recommendation).
  • Operation between 0 and 60ºC and between 0 and 80% of RH.